Treating bore or tank water for drinking on a remote site starts with assessing and testing the source, protecting the bore or tank, filtering out particles, and disinfecting the water. Where testing picks up arsenic, nitrate, iron or high salinity, extra treatment is needed beyond filtration and disinfection. Only testing shows what is in a local supply, so a specialist should design the system. Sky Drop makes drinking water from air; we do not treat bore or tank water or sell treatment kits.
What risks come with bore and tank water on a remote site?
Bore and tank supplies can carry disease-causing microorganisms, naturally occurring minerals and chemical contaminants, depending on how water is drawn, stored and piped.
Start with a simple flow diagram of water sources, treatment or disinfection units, service tanks and major piping, then assess groundwater chemical and microbial quality as a priority. Human and livestock wastes are the greatest microbial hazards, especially where septic discharge or stock reach watercourses or bores. Naturally occurring arsenic, fluoride and uranium, or agricultural nitrates, can also exceed safe levels in parts of Australia.
Deep groundwater from confined aquifers tens to hundreds of metres down is isolated from surface conditions and less prone to contamination, though it can carry high mineral levels. Shallow groundwater in unconfined aquifers recharges over days and weeks, leaving it prone to organic pollutants and effluents. Untreated warm water at 25 to 40 degrees C can grow Naegleria fowleri in dams, hoses and long above-ground pipelines; under Queensland Health guidance, deep artesian bores in rural Queensland carry particular risk when warm water cools in open dams before travelling above ground to tanks.. If affected water goes up the nose, it can cause primary amoebic meningoencephalitis, a rare and usually fatal illness. Testing is specialised, and a negative result does not guarantee the water is free of it.
Rainwater tanks bring accumulated sediment, mosquitoes where inlets and overflows lack mosquito-proof mesh, and pipework holding stagnant water. Whenever microbial quality is in doubt, disinfect or boil rainwater before use.
Which treatment steps do health agencies describe for bore and tank water?
Private drinking water treatment uses filtration, ultraviolet disinfection, chlorination, or a combination of those stages in sequence, with boiling as an emergency option for small quantities.
Treatment matters especially where vulnerable people live or visit, and employers have a duty of care to provide safe drinking water. Queensland Health guidance puts filtration first: filters remove sediment plus some chemicals, algal toxins and microorganisms, and are normally paired with ultraviolet disinfection, chlorination or both. Maintain and replace filters per the manufacturer's advice.
Ultraviolet (UV) disinfection kills or inactivates bacteria, viruses and protozoa, but cannot penetrate dirty or cloudy water, so filtration must precede it. Most UV lamps need replacing every 12 months. Use UV at the point of use or with chlorination to stop biofilms growing in downstream pipework; when both are used, UV goes first because UV light can break down chlorine.
Chlorination covers a wide range of contaminants and also needs filtration first. Chlorine is a hazardous chemical: handle, store and use it only per label instructions, and avoid stabilised chlorine containing isocyanuric acid in enclosed tanks, where it is ineffective.
For small quantities in an emergency when water quality is uncertain, Western Australia's Department of Health advises heating water to a rolling boil for at least 1 minute to kill disease-causing microorganisms. For broader options, see how you can purify water off-grid.
Which bore and tank water problems need which treatment?
Filtration and disinfection handle microbes and cloudiness, whereas iron, arsenic, nitrate and high salinity require targeted chemical or membrane treatment designed around lab results.
The table below lists common bore and tank water problems and the treatment health sources describe.
| Problem | Guideline or note | Usual treatment per the sources |
|---|---|---|
| Microbes from stock, septic waste or a poorly protected bore | Greatest microbial hazards are human and livestock wastes (NHMRC) | Filtration, ultraviolet disinfection, chlorination, or a combination (Queensland Health) |
| Cloudy water | UV light cannot penetrate dirty or cloudy water | Filtration first, then UV or chlorine (Queensland Health) |
| Iron | Aesthetic guideline of 0.3 mg/L, no health-based value | Coagulation then filtration; groundwater with high iron can be treated with aeration, oxidation with chlorine, pH adjustment or lime softening (NHMRC) |
| Arsenic | Health guideline 0.01 mg/L | Conventional coagulation, after converting trivalent arsenic to the pentavalent form by oxidation; lime softening can also work (NHMRC) |
| Nitrate and nitrite | Nitrate 50 mg/L (protects bottle-fed infants under 3 months; up to 100 mg/L for adults and children over 3 months); nitrite 3 mg/L | Conventional treatment is not effective for nitrate; removal uses anion exchange resins and is expensive to operate (NHMRC) |
| High dissolved solids (salinity) | 600 mg/L for palatability; no health value | Difficult to remove; reverse osmosis, ion exchange and distillation need considerable energy; lime softening where hardness is the cause (NHMRC) |
| Naegleria fowleri in warm water | Grows in untreated water at 25 to 40 degrees C, including long above-ground pipelines from artesian bores | Chlorination, filtration and UV can kill or remove it; seek expert advice (Queensland Health) |
Sources: National Health and Medical Research Council (Australian Drinking Water Guidelines) and Queensland Health (Safe water on rural properties, 2015).
Reading lab results against these thresholds shows why a specialist needs the figures before designing a system. Water with total dissolved solids between 600 and 900 mg/L sits in the fair palatability band above the 600 mg/L guideline, and iron above 0.3 mg/L affects taste and precipitation with no health limit. Arsenic above 0.01 mg/L or nitrite above 3 mg/L breaches a health limit, and nitrate above 50 mg/L requires notifying the health authority so parents can use rainwater or bottled water for bottle-fed infants under 3 months, though adults and children over 3 months can consume up to 100 mg/L.
How do you check that bore and tank water treatment is still working?
Keeping treated water safe depends on regular inspections of the source, storage and pipework alongside frequent disinfection checks, because lab tests alone are not enough.
Under National Health and Medical Research Council monitoring advice for small, remote water supplies, microbial tests are a useful backup that cannot replace checking source protection, treatment and barrier integrity to the tap. Testing a narrow range of key characteristics frequently works better than infrequent comprehensive analyses. Weekly inspections are preferred for small remote supplies, covering the catchment, sealed boreheads, fences around bores and tanks, tank roofs, above-ground pipes, valves and bore drainage, plus checks after heavy rain, flooding or storms. Disinfection is a critical control point: monitor it continuously with alarms where possible, or check chlorine residual or UV power and operation manually several times a day.
Schedules differ by jurisdiction: Queensland Health suggests monthly checks that the bore head and fittings are watertight and protected from surface flows, the bore is fenced and locked, and the pump and piping are maintained.
For rainwater tanks, routine checks include inspecting stored water for mosquito larvae at least every six months and checking every 2 to 3 years for accumulated sediment.
When does making drinking water from air suit a remote site?
Making drinking water from air suits a remote site when groundwater or tank water has poor quality, high salinity or chemical contamination, or when running multi-stage bore treatment is impractical.
An atmospheric water generator cools air below its dew point so water vapour condenses, instead of drawing water from a bore or roof. Sky Drop machines operate in 15 to 40 degrees C and at least 35% humidity, make less water in dry air, and run on mains power, a generator or solar. The Sky Drop 100 Solar is solar-ready on 48 V DC and needs about 30 kWh a day of solar (panels, battery and inverter are not included); other models run on mains power. Water passes through sediment, reverse osmosis and carbon filtration with sterilisation. Sky Drop is having its machines tested against the Australian Drinking Water Guidelines and will publish the results.
Where tap water is good, use it. For remote water supply across mine sites and remote camps, construction sites, farms and emergency response sites, Sky Drop supplies atmospheric water generators Australia-wide from NSW, primarily on rental plans including servicing, with purchase as a second option. You can also compare atmospheric water, bottled water and water carting.
To check whether an atmospheric water generator fits your site's power and climate, call 1300 232 004 or request a free site consultation through our contact page; our Australian team calls back within one business day.